Wednesday 19 March 2014

Parallel operation of transformers

Why Parallel Operation of Transformers is required ?
   
                        When load demand increases we have to use more transformers. ie,for meet a load which is more than the rating of the existing transformer,a second transformer connected in parallel with it.

 Advantages of Parallel Operation of Transformers.

1)To maximize the efficiency of electrical power system :

         Power transformer gives the maximum efficiency when they works on full load. By connecting numbers of transformers in parallel, we can switch on only those transformers which will give the total demand by running nearer to its full load rating for that time. When load increases we can switch on more transformers one by one that are connected in parallel to meet the total demand similarly when load decreases we can turn off  transformers one by one. In this way we can run the system with maximum efficiency.

2)To maximize electrical power system availability:
            If numbers of transformers run in parallel we can take shutdown any one of them for maintenance purpose. Other parallel transformers in system will meet the total demand of the system.

3)To maximize power system reliability:
             If any one of the transformers run in parallel, is tripped due to fault other parallel transformers is the system will share the load.So electrical system  not interrupted by tripping of one transformer ,if the shared loads do not make other transformers over loaded.

4)To maximize electrical power system flexibility:
             By using parallel connection we can connect a number of transformers in addition to existing system to meet our required load very easily.If the load is increased in future more than the available capacity,just connect more transformers in parallel.If the demand is decreased remove a transformer from the system.

Conditions for Parallel Operation of Transformers

When two or more transformers are run in parallel their primary windings are connected to supply bus bars and secondaries are connected to load bus bar.When connecting two or more transformers in parallel certain  conditions has to be met for satisfactory performance. These are the conditions for parallel operation of transformers.
a) same polarity.
b) same voltage ratio of transformer
c) same percentage impedance.
d)Same Phase Sequence

Same Polarity
                            Transformers should be properly connected with regarding to its polarity.The polarity of the transformers connected in parallel should be same otherwise it may lead to dead short circuit.When connecting two or more transformers in parallel it is essential that their terminals of similar polarities should joined to same bus bar.bar. Otherwise emfs induced in the secondaries will be in opposite polarities and they acts as a short circuit even for no load.Polarity of transformer means the direction of induced emf in secondary. If the directions of induced secondary emf in two transformers are opposite to each other when same input power is fed to the both of the transformers, the transformers are said to be in opposite polarity. If the directions of induced secondary emf in two transformers are same when same input power is fed to the both of the transformers, the transformers are said to be in same polarity.

Same Voltage Ratio
                               The voltage ratio of the  transformers*( turns ratio) which are connected in parallel should be kept equal in order to avoid losses occurring in transformers due to load circulating currents.If two transformers connected in parallel have a slight different in their voltage ratio ,the parallel operation is possible.But due to the difference in volt ratio even the primary supply voltage is identical there will be a difference in secondary voltages even in no load condition.So there will be a circulating current between secondaries and therefore between primaries also.This circulating current makes unequal loading conditions,so transformers in parallel system may be overloaded. As the internal impedance of transformer is small, a small voltage difference may cause sufficiently high circulating current causing unnecessary extra I2R loss.

Same Percentage Impedance
                              If the impedance of transformers which are connected in parallel are not same, then the parallel operation is possible but the power factor at which two transformer operates will be different from the common load .So the transformers will not share load in proportional to their KVA ratings.
                             In other words,The current shared by two transformers running in parallel is strictly depends on  their KVA ratings. As we know electric current carried by these transformers are inversely proportional to their internal impedance. From these two statements it can be said that impedance of transformers running in parallel are inversely proportional to their KVA ratings.So if the impedance are not identical ,load sharing will also be different.
                      Identical percentage impedance of two different transformers is difficult to achieve practically that is why the transformers run in parallel may not have exactly same percentage impedance but the values would be as nearer as possible.

Same Phase Sequence
                           The phase sequence or the order in which the phases reach their maximum positive voltage, must be identical for two parallel transformers. Otherwise, during the cycle, each pair of phases will be short circuited.

6 comments:

  1. SIMPLE & PRECISE EXPLANATION OF THE MATTER

    ReplyDelete
  2. A winding machine has included with metal wire, string or paper, onto an inside, spool, or bobbin, which are unmistakable sorts of bowing machines from direct manual manage machines to complex PC numeric control (CNC) machines. In light of current conditions, the titanic piece of the winding machines has turn winding, rope winding, and continuing on fiber winding.toroidal winding machine

    ReplyDelete
  3. An Automatic winding machine is using in the particular target objective, which is confront the necessities are high profitability, high return, customized demonstrate normally used long linkage layout.toroidal winding machine

    ReplyDelete
  4. Utilizing veneer copper winding wire Motors will convey greater development and high outcomes. Transformers made of Enamel Copper Wire will lose less imperativeness.

    The other element of these wires is that make them more intelligent for use in these items is its protection from disintegration.toroidal winding machine

    ReplyDelete
  5. Yeah! If two or more transformer is connected in parallel, then what is the load sharing % between them is according to their rating.

    Power Transformers in India | Transformer Manufacturer in India

    ReplyDelete